2109966555
Fax: +30 210 9969444
E-mail: info@acepower.gr
HIGHLIGHTS
Sentinel Dual is the best solution for powering mission critical applications and electro-medical devices requiring maximum power reliability.
Flexibility of installation and use (digital display, user-replaceable battery set), as well as the many communication options available, makes the Sentinel Dual suitable for many different applications from IT to security.
Up to 3 Sentinel Duals can be operated in parallel in either capacity or N+1 redundant configuration offering increased reliability for critical system. The Sentinel Dual can be installed as Tower (floor standing) or Rack, ideal for network and server rack applications.
The Sentinel Dual range is available in 4-5-6-8-10 KVA/kW models with on-line double conversion technology (VFI): the load is powered continuously by the inverter which supplies a sinusoidal voltage, filtered and stabilised in terms of voltage, form and frequency. In addition, the input and output filters significantly increase the load’s immunity to mains disturbances and lightning strikes.
Technology and performance: selectable Economy Mode and Smart Active Mode functions.
Diagnostics: Standard digital display, RS232 and USB interfaces with PowerShield3 software downloadable, communications slot for connectivity accessories.
Simplified installation
Operating mode selection
Functions can be programmed via software or manually via the front display panel.
High quality output voltage
High battery reliability
Emergency function
This configuration ensures the operation of those emergency systems that require continuous, reliable and long-lasting power supply in the event of a mains power failure, such as emergency lighting, fire detection/extinguishing systems and alarms. When the mains power supply fails, the inverter begins powering the loads with a progressive start-up (Soft Start) in order to prevent overload.
Battery optimisation
The wide input voltage range and a high hold-up time minimise battery usage and increase efficiency and battery life; for smaller power breaks, energy is drawn from a group of appropriately-sized capacitors.
EnergyShare
10 A configurable IEC output sockets allow for runtime optimisation by programming the switching off of low priority loads on mains failure; alternatively, emergency loads that are normally not powered when mains is present can be activated.
Other features
Advanced communications
Unity Power Factor
MODELS | SDU 4000 | SDU 5000
SDU 5000 PDIST |
SDU 6000
SDU 6000 PDIST |
SDU 6000 ER | SDU 8000 TM | SDU 10000 TM | SDU 10000 DI | SDU 10000 DI ER | SDU 8000 TM | SDU 10000 TM | |
INPUT |
|||||||||||
Dual Input | no | yes | no | ||||||||
Nominal Voltage | 220-230-240 VAC | 380-400-415 VAC
(3W + N + PE) 220/230/240 (1W + N + PE) |
|||||||||
Voltage tolerance | 230 VAC ±20% | 400 VAC ±20%
230 VAC ±20% |
|||||||||
Minimum Voltage | 184 VAC | 318 / 184 VAC | |||||||||
Nominal frequency | 50/60 Hz ± 5Hz | ||||||||||
Power factor | > 0,98 | ||||||||||
Current distortion | ≤5% | ||||||||||
BYPASS |
|||||||||||
Voltage tolerance | 180 – 264 VAC ( selectable in Economy Mode or Smart Active Mode) | ||||||||||
Frequency tolerance | Selectable frequency ± 5% (selected by user) | ||||||||||
Overload | 110% continuous, 130% for 1 hour, 150% for 10 minutes, over 150% for 3 seconds | ||||||||||
OUTPUT |
|||||||||||
Nominal power (VA) | 4000 | 5000 | 6000 | 6000 | 8000 | 10000 | 10000 | 10000 | 8000 | 10000 | |
Active power (W) | 3600 | 5000 | 6000 | 6000 | 8000 | 10000 | 10000 | 10000 | 8000 | 10000 | |
Nominal Voltage | 220-230-240 VAC selectable | ||||||||||
Voltage distortion | ≤ 3% with linear load / 6% with non-linear load | <1% with linear load / <3% with non-linear load | |||||||||
Frequency | 50/60 Hz selectable | ||||||||||
Static variation | 1,5% | ||||||||||
Dynamic variation | ≤5% in 20 ms | ||||||||||
Waveform | Sinusoidal | ||||||||||
Crest factor | 3:1 | ||||||||||
BATTERIES |
|||||||||||
Type | VRLA AGM maintenance-free lead acid | ||||||||||
Recharge Time | 4-6 hours | ||||||||||
OTHER FEATURES |
|||||||||||
Net weight (kg) | 38 | 46 | 47 | 19 | 21+60 | 22+65 | 22+65 | 23 | 19+53 | 20+62 | |
Gross weight (kg) | 43 | 52 | 53 | 25 | 27+66 | 28+71 | 28+71 | 29 | 83 | 93 | |
Dimensions (WxDxH) (mm) |
131x 640 x 448 tower 19″ x 640 x 3U rack |
2 x (131x 640 x 448) tower – 2 x (19″ x 640 x 3U) rack ER version(131x 640 x 448) tower – (19″ x 640 x 3U) rack |
2 x (131x 640 x 448) tower – 2 x (19″ x 640 x 3U) rack | ||||||||
Package dimensions (WxDxH) (mm) | 780 x 555 x (270+15) |
2 x (780 x 555 x 270) + H 15 ER version 780 x 555 x (270+15) |
2 x (780 x 555 x 270) + H 15 | ||||||||
Efficiency | up to 95% on line, 98% eco mode | ||||||||||
Protections | Overcurrent – short-circuit – overvoltage – undervoltage – overtemperature – excessive low battery | ||||||||||
Parallel Operation | Optional Parallel Card | ||||||||||
Communications | USB /RS232 / Slot for communications interface / REPO + Input contact | ||||||||||
Input Connection | Terminal block | ||||||||||
Output sockets | Terminal block +2 IEC 320 C13 + 1 IEC 320 C19 | Terminal block +8 IEC 320 C13 + 2 IEC 320 C20 | Terminal block +2 IEC 320 C13 + 2 IEC 320 C20 | Terminal block +2 IEC 320 C13 + 3 IEC 320 C19 | |||||||
Operating temperature | 0 ° C/ +40 ° C | ||||||||||
Relative humidity | <95% non-condensing | ||||||||||
Color | Black RAL 9005 | ||||||||||
Noise level at 1 m (ECO Mode) | < 48 dBA | ||||||||||
Standard equipment provided | USB cable, handles kit |