Home » Products » UPS » Line Interactive » Net Power (600 – 2000 VA)
The Net Power series is available in 600 – 2000 VA models with digital technology: when available the load is supplied from the mains power supply, which is amplitude- stabilised by the automatic voltage regulator (AVR) and filtered against overvoltages by EMI filters. When the mains fails, the load is powered from a pseudo-sine wave inverter, to provide sufficient runtime for computer system shutdown using PowerShield3 software, which can be downloaded free from www.riello-ups.com
Advanced communications
MODELS | NPW 600 | NPW 800 | NPW 1000 | NPW 1500 | NPW 2000 | |
POWER | 600VA/360W | 800VA/480W | 1000VA/600W | 1500VA/900W | 2000VA/1200W | |
INPUT |
||||||
Nominal Voltage | 220-230-240 VAC | |||||
Input Voltage tolerance | 230 VAC (± 25%) | |||||
Frequency | 50/60 Hz with automatic selection | |||||
OUTPUT |
||||||
Voltage during mains operation | 230 VAC (-8%, + 10%) | |||||
Voltage during battery operation | 230 VAC (+/- 5%) | |||||
Frequency during battery operation | 50 ή 60 Hz (+/- 0,5%) | |||||
Battery waveform | Pseudo sinusoidal | |||||
BATTERIES |
||||||
Type | VRLA AGM maintenance-free lead based | |||||
Recharge Time | 6-8 h | 2-4 h | ||||
OTHER FEATURES | ||||||
Net weight (kg) | 4.3 | 4.9 | 8 | 11.1 | 11.5 | |
Dimensions (WxDxH) (mm) | 100 x 287 x 142 | 146 x 350 x 160 | 146 x 397 x 205 | |||
Protections | Excessive low battery – overvoltage – short circuit | |||||
Communications | USB | USB + RS232 | ||||
Output sockets | 4 x IEC 320 C13 sockets | 6 x IEC 320 C13 sockets | ||||
Standards | EN 62040-1-1 and Directive 2006/95/EC;
EN 62040-2 category C2 and Directive 2004/108 EC |
|||||
Certificates | CE | |||||
Operating temperature | 0 – 40 ° C | |||||
Colour | Black | |||||
Altitude and relative humidity | 6000 m max altitude, <95% non-condensing | |||||
Standard equipment | 2 cables for powering loads; user manual |