Master MPS (10-200 KVA)

Master MPS (10-200 KVA)
3:1 10-100KVA
3:3 10-200KVA

On Line UPS

Master MPS series UPS provide maximum protection and power quality for mission critical loads, including data centres, industrial processes, telecommunications, security and electro-medical systems. Master MPS is an on-line double conversion UPS (VFI SS 111 – IEC EN 62040-3) with a transformer isolated inverter.
The Master MPS range includes three-phase input and single-phase output versions from 10 to 100 kVA, and three-phase input and output versions from 10 to 800 KVA.
All versions are provided with a 6-pulse thyristor-based rectifier, with or without optional harmonic filters.

A 12-pulse thyristor-based rectifier is available on request for the 60 and 80 KVA versions with or without optional harmonic filters.

Features

Master MPM 10-100

Master MPT 10-80

Master MPT 100-200

Product Brochure

Flexibility

Master MPS is suitable for a wide range of applications including IT and the most demanding industrial environments. The UPS is suitable for power capacitive loads such as blade servers, from 0,9 leading to 0,8 lagging. With a broad range of accessories and options, complex configurations and system architectures can be achieved to guarantee maximum power availability and the option to add new UPS without interruption to existing installation.

Battery care system: maximum battery care

Normally the batteries are kept charged by the rectifier; when mains power fails, the UPS uses this energy source to power the consumers. Proper battery care is therefore critical to ensuring correct UPS operation under emergency conditions. The Riello UPS battery care system consists of a series of functions designed to optimise battery management and achieve the best performance and operating life possible. Master MPS is also compatible with different battery technologies: vented open lead acid, VRLA AGM, Gel, NiCd, Flywheels, Supercaps and Lithium.

  Advanced communications

  • Advanced multi-platform communications for all operating systems and network environments: PowerShield3 monitoring and shutdown software included for Windows operating systems 8, 7, Hyper-V, 2012, 2008, and previous versions, Mac OS X, Linux, VMWare ESXi, Citrix XenServer and other Unix operating systems.
  • Compatible with TeleNetGuard remote monitoring service
  • RS232 serial and USB ports
  • 3 slots for the installation of optional communications accessories such as network adapters, potential free contacts, etc.
  • REPO Remote Emergency Power Off for switching off the UPS via a remote emergency button
  • Input for the connection of the auxiliary contact of an external manual bypass
  • Input for synchronisation from an external source
  • Graphic display panel for remote connection.

Maximum reliability and availability

  • Distributed or centralised parallel configuration of up to 8 units per redundant (N+1) or power parallel system. Parallel configurations using models with different power ratings are also possible.
  • Hot System Expansion (HSE): allows the addition of a further UPS into an existing system, without the need to switch off the existing UPS or transfer them to bypass mode. This guarantees maximum load protection, even during maintenance and system expansion.
  • Maximum levels of availability, even in the event of an interruption to the parallel bus cable: the system is “FAULT TOLERANT”. It is not affected by connection cable faults and continues powering the load without disruption, signalling an alarm condition.
  • Efficiency Control System (ECS): a system to optimise the operating efficiency of parallel systems, according to the power required by the load. N +1 redundancy is guaranteed, with every UPS working in parallel at the best load level possible to achieve higher overall efficiency.

Options

  • UPS Group Synchroniser (UGS)

    Allows two or more non-parallel UPS devices to remain synchronised even during mains power failure.The UGS also enables a Riello UPS to be synchronised with another power source that is independent and of a different power rating.

  • Parallel Systems Joiner (PSJ)

    Allows two groups of UPS to be connected in parallel whilst operating, in the event of maintenance (with no interruption to the output), using a power coupling switch. Should one of the UPS in one of the parallel groups fail, it is automatically excluded.The PSJ connects the remaining UPS, to the other parallel group via an external bypass, in order to continue to guarantee load redundancy.

MODEL MPM 10 MPM 15 MPM 20 MPM 30 MPM 40 MPM 60 MPM 80 MPM 100

INPUT

Nominal Voltage 380 – 400 – 415 VAC three-phase
Voltage tolerance 400 V + 20% /- 25%
Frequency 45 – 65 Hz
Soft start 0 – 100% in 120’’ (selectable)
Permitted frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard equipment provided Back Feed protection; separable bypass line

BY PASS

Nominal voltage 220 – 230 – 240 VAC single-phase + N
Nominal frequency 50 or 60 Hz (selectable)

OUTPUT

Nominal power (kVA) 10 15 20 30 40 60 80 100
Active power (kW) 9 13,5 18 27 36 54 72 90
Number of phases 1
Nominal voltage 220 – 230 – 240 VAC single-phase + N (selectable)
Static stability ± 1%
Dynamic stability ± 5% in 10 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor 3:1 lpeak/lrms
Frequency stability on battery 0,05%
Frequency 50 or 60 Hz (selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’

BATTERIES

Type VRLA AGM / GEL; NiCd; Li-ion;
Residual ripple voltage < 1%
Temperature compensation (-0,5) Vx°C
Typical charge current 0,2 x C10

INFO FOR INSTALLATION

Weight without batteries (kg) 200 220 230 270 302 440 500 580
Dimensions (WxDxH) (mm) 555 x 740 x 1400 800 x 740 x 1400 800 x 800 x 1900
Remote signals dry contacts
Remote controls ESD and bypass
Communications  Double RS232 + dry contacts + 2 slots for communications interface
Operating temperature 0 – 40 ° C
Relative humidity <95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) 60 dBA 62 dBA
IP rating IP20
Smart Active efficiency up to 98%
Standards Directives LV 2006/95/EC – 2004/108/EC; Safety IEC EN 62040-1;

EMC IEC EN 62040-2; Performance IEC EN 62040-3

Classification in accordance

with IEC 62040-3

(Voltage Frequency Independent) VFI – SS – 111
Moving the UPS transpallet

MODELS MPT 10 MPT 15 MPT 20 MPT 30 MPT 40 MPT 60 MPΤ 80

INPUT

Nominal Voltage 380 – 400 – 415 VAC three-phase
Voltage tolerance 400 V + 20% /- 25%
Frequency 45 – 65 Hz
Soft start 0 – 100% in 120’’ (selectable)
Permitted frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard equipment provided Back Feed protection; separable bypass line

BY PASS

Nominal voltage 360 – 400- 420 VAC three-phase + N
Nominal frequency 50 or 60 Hz (selectable)

OUTPUT

Nominal power (KVA) 10 15 20 30 40 60 80
Active power (KW) 9 13,5 18 27 36 54 72
Number of phases 3 + N
Nominal voltage 380 – 400 – 415 VAC three-phase + N (selectable)
Static stability ± 1%
Dynamic stability ± 5% in 10 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor 3:1 lpeak/lrms
Frequency stability on battery 0,05%
Frequency 50 or 60 Hz (selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’

BATTERIES

Type VRLA AGM / GEL; NiCd; Li-ion;
Residual ripple voltage < 1%
Temperature compensation (-0,5) Vx°C
Typical charge current 0,2 x C10

INFO FOR INSTALLATION

Weight without batteries (kg) 228 241 256 315 335 460 540
Dimensions (WxDxH) (mm) 555 x 740 x 1400 800 x 740 x 1400
Remote signals dry contacts
Remote controls ESD and bypass
Communications  Double RS232 + dry contacts + 2 slots for communications interface
Operating temperature 0 – 40 ° C
Relative humidity <95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) 60 dBA 62 dBA
IP rating IP20
Smart Active efficiency up to 98%
Standards Directives LV 2006/95/EC – 2004/108/EC; Safety IEC EN 62040-1;

EMC IEC EN 62040-2; Performance IEC EN 62040-3

Classification in accordance

with IEC 62040-3

(Voltage Frequency Independent) VFI – SS – 111
Moving the UPS transpallet

MODELS MPT 100 MPT 120 MPT 160 MPT 200

INPUT

Nominal Voltage 380 – 400 – 415 VAC three-phase
Voltage tolerance 400 V + 20% /- 25%
Frequency 45 – 65 Hz
Soft start 0 – 100% in 120’’ (selectable)
Permitted frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard equipment provided Back Feed protection; separable bypass line

BY PASS

Nominal voltage 360 – 400 – 420 VAC three-phase + N
Nominal frequency 50 or 60 Hz (selectable)
OUTPUT  
Nominal power (KVA) 100 120 160 200
Active power (KW) 90 108 144 180
Number of phases 3 + N
Nominal voltage 380 – 400 – 415 VAC three-phase + N (selectable)
Static stability ± 1%
Dynamic stability ± 5% σε 10 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor 3:1 lpeak/lrms
Frequency stability on battery 0,05%
Frequency 50 or 60 Hz (selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’

BATTERIES

Type VRLA AGM / GEL; NiCd; Li-ion;
Residual ripple voltage < 1%
Temperature compensation (-0,5) Vx°C
 Typical charge current 0,2 x C10

INFO FOR INSTALLATION

Weight 600 610 690 790
Dimensions (WxDxH) (mm) 800 x 800 x 1900
Remote signals dry contacts
Remote controls ESD and bypass
Communications Double RS232 + dry contacts + 2 slots for communications interface
Operating temperature 0 – 40 ° C
Relative humidity <95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) 65 dBA 68 dBA
IP rating IP20
Smart Active efficiency έως 98%
Standards Directives LV 2006/95/EC – 2004/108/EC; Safety IEC EN 62040-1;

EMC IEC EN 62040-2; Performance IEC EN 62040-3

Classification in accordance

with IEC 62040-3

(Voltage Frequency Independent) VFI – SS – 111