Master MPS series UPS provide maximum protection and power quality for mission critical loads, including data centres, industrial processes, telecommunications, security and electro-medical systems. Master MPS is an on-line double conversion UPS (VFI SS 111 – IEC EN 62040-3) with a transformer isolated inverter.
The Master MPS range includes three-phase input and single-phase output versions from 10 to 100 kVA, and three-phase input and output versions from 10 to 800 KVA.
All versions are provided with a 6-pulse thyristor-based rectifier, with or without optional harmonic filters.
A 12-pulse thyristor-based rectifier is available on request for the 60 and 80 KVA versions with or without optional harmonic filters.
Flexibility
Master MPS is suitable for a wide range of applications including IT and the most demanding industrial environments. The UPS is suitable for power capacitive loads such as blade servers, from 0,9 leading to 0,8 lagging. With a broad range of accessories and options, complex configurations and system architectures can be achieved to guarantee maximum power availability and the option to add new UPS without interruption to existing installation.
Battery care system: maximum battery care
Normally the batteries are kept charged by the rectifier; when mains power fails, the UPS uses this energy source to power the consumers. Proper battery care is therefore critical to ensuring correct UPS operation under emergency conditions. The Riello UPS battery care system consists of a series of functions designed to optimise battery management and achieve the best performance and operating life possible. Master MPS is also compatible with different battery technologies: vented open lead acid, VRLA AGM, Gel, NiCd, Flywheels, Supercaps and Lithium.
Advanced communications
Maximum reliability and availability
Options
Allows two or more non-parallel UPS devices to remain synchronised even during mains power failure.The UGS also enables a Riello UPS to be synchronised with another power source that is independent and of a different power rating.
Allows two groups of UPS to be connected in parallel whilst operating, in the event of maintenance (with no interruption to the output), using a power coupling switch. Should one of the UPS in one of the parallel groups fail, it is automatically excluded.The PSJ connects the remaining UPS, to the other parallel group via an external bypass, in order to continue to guarantee load redundancy.
MODEL | MPM 10 | MPM 15 | MPM 20 | MPM 30 | MPM 40 | MPM 60 | MPM 80 | MPM 100 |
INPUT |
||||||||
Nominal Voltage | 380 – 400 – 415 VAC three-phase | |||||||
Voltage tolerance | 400 V + 20% /- 25% | |||||||
Frequency | 45 – 65 Hz | |||||||
Soft start | 0 – 100% in 120’’ (selectable) | |||||||
Permitted frequency tolerance | ± 2% (selectable from ± 1% to ± 5% from front panel) | |||||||
Standard equipment provided | Back Feed protection; separable bypass line | |||||||
BY PASS |
||||||||
Nominal voltage | 220 – 230 – 240 VAC single-phase + N | |||||||
Nominal frequency | 50 or 60 Hz (selectable) | |||||||
OUTPUT |
||||||||
Nominal power (kVA) | 10 | 15 | 20 | 30 | 40 | 60 | 80 | 100 |
Active power (kW) | 9 | 13,5 | 18 | 27 | 36 | 54 | 72 | 90 |
Number of phases | 1 | |||||||
Nominal voltage | 220 – 230 – 240 VAC single-phase + N (selectable) | |||||||
Static stability | ± 1% | |||||||
Dynamic stability | ± 5% in 10 ms | |||||||
Voltage distortion | < 1% with linear load / < 3% with non-linear load | |||||||
Crest factor | 3:1 lpeak/lrms | |||||||
Frequency stability on battery | 0,05% | |||||||
Frequency | 50 or 60 Hz (selectable) | |||||||
Overload | 110% for 60’; 125% for 10’; 150% for 1’ | |||||||
BATTERIES |
||||||||
Type | VRLA AGM / GEL; NiCd; Li-ion; | |||||||
Residual ripple voltage | < 1% | |||||||
Temperature compensation | (-0,5) Vx°C | |||||||
Typical charge current | 0,2 x C10 | |||||||
INFO FOR INSTALLATION |
||||||||
Weight without batteries (kg) | 200 | 220 | 230 | 270 | 302 | 440 | 500 | 580 |
Dimensions (WxDxH) (mm) | 555 x 740 x 1400 | 800 x 740 x 1400 | 800 x 800 x 1900 | |||||
Remote signals | dry contacts | |||||||
Remote controls | ESD and bypass | |||||||
Communications | Double RS232 + dry contacts + 2 slots for communications interface | |||||||
Operating temperature | 0 – 40 ° C | |||||||
Relative humidity | <95% non-condensing | |||||||
Colour | Dark grey RAL 7016 | |||||||
Noise level at 1 m (ECO Mode) | 60 dBA | 62 dBA | ||||||
IP rating | IP20 | |||||||
Smart Active efficiency | up to 98% | |||||||
Standards | Directives LV 2006/95/EC – 2004/108/EC; Safety IEC EN 62040-1;
EMC IEC EN 62040-2; Performance IEC EN 62040-3 |
|||||||
Classification in accordance
with IEC 62040-3 |
(Voltage Frequency Independent) VFI – SS – 111 | |||||||
Moving the UPS | transpallet |
MODELS | MPT 10 | MPT 15 | MPT 20 | MPT 30 | MPT 40 | MPT 60 | MPΤ 80 |
INPUT |
|||||||
Nominal Voltage | 380 – 400 – 415 VAC three-phase | ||||||
Voltage tolerance | 400 V + 20% /- 25% | ||||||
Frequency | 45 – 65 Hz | ||||||
Soft start | 0 – 100% in 120’’ (selectable) | ||||||
Permitted frequency tolerance | ± 2% (selectable from ± 1% to ± 5% from front panel) | ||||||
Standard equipment provided | Back Feed protection; separable bypass line | ||||||
BY PASS |
|||||||
Nominal voltage | 360 – 400- 420 VAC three-phase + N | ||||||
Nominal frequency | 50 or 60 Hz (selectable) | ||||||
OUTPUT |
|||||||
Nominal power (KVA) | 10 | 15 | 20 | 30 | 40 | 60 | 80 |
Active power (KW) | 9 | 13,5 | 18 | 27 | 36 | 54 | 72 |
Number of phases | 3 + N | ||||||
Nominal voltage | 380 – 400 – 415 VAC three-phase + N (selectable) | ||||||
Static stability | ± 1% | ||||||
Dynamic stability | ± 5% in 10 ms | ||||||
Voltage distortion | < 1% with linear load / < 3% with non-linear load | ||||||
Crest factor | 3:1 lpeak/lrms | ||||||
Frequency stability on battery | 0,05% | ||||||
Frequency | 50 or 60 Hz (selectable) | ||||||
Overload | 110% for 60’; 125% for 10’; 150% for 1’ | ||||||
BATTERIES |
|||||||
Type | VRLA AGM / GEL; NiCd; Li-ion; | ||||||
Residual ripple voltage | < 1% | ||||||
Temperature compensation | (-0,5) Vx°C | ||||||
Typical charge current | 0,2 x C10 | ||||||
INFO FOR INSTALLATION |
|||||||
Weight without batteries (kg) | 228 | 241 | 256 | 315 | 335 | 460 | 540 |
Dimensions (WxDxH) (mm) | 555 x 740 x 1400 | 800 x 740 x 1400 | |||||
Remote signals | dry contacts | ||||||
Remote controls | ESD and bypass | ||||||
Communications | Double RS232 + dry contacts + 2 slots for communications interface | ||||||
Operating temperature | 0 – 40 ° C | ||||||
Relative humidity | <95% non-condensing | ||||||
Colour | Dark grey RAL 7016 | ||||||
Noise level at 1 m (ECO Mode) | 60 dBA | 62 dBA | |||||
IP rating | IP20 | ||||||
Smart Active efficiency | up to 98% | ||||||
Standards | Directives LV 2006/95/EC – 2004/108/EC; Safety IEC EN 62040-1;
EMC IEC EN 62040-2; Performance IEC EN 62040-3 |
||||||
Classification in accordance
with IEC 62040-3 |
(Voltage Frequency Independent) VFI – SS – 111 | ||||||
Moving the UPS | transpallet |
MODELS | MPT 100 | MPT 120 | MPT 160 | MPT 200 | ||
INPUT |
||||||
Nominal Voltage | 380 – 400 – 415 VAC three-phase | |||||
Voltage tolerance | 400 V + 20% /- 25% | |||||
Frequency | 45 – 65 Hz | |||||
Soft start | 0 – 100% in 120’’ (selectable) | |||||
Permitted frequency tolerance | ± 2% (selectable from ± 1% to ± 5% from front panel) | |||||
Standard equipment provided | Back Feed protection; separable bypass line | |||||
BY PASS |
||||||
Nominal voltage | 360 – 400 – 420 VAC three-phase + N | |||||
Nominal frequency | 50 or 60 Hz (selectable) | |||||
OUTPUT | ||||||
Nominal power (KVA) | 100 | 120 | 160 | 200 | ||
Active power (KW) | 90 | 108 | 144 | 180 | ||
Number of phases | 3 + N | |||||
Nominal voltage | 380 – 400 – 415 VAC three-phase + N (selectable) | |||||
Static stability | ± 1% | |||||
Dynamic stability | ± 5% σε 10 ms | |||||
Voltage distortion | < 1% with linear load / < 3% with non-linear load | |||||
Crest factor | 3:1 lpeak/lrms | |||||
Frequency stability on battery | 0,05% | |||||
Frequency | 50 or 60 Hz (selectable) | |||||
Overload | 110% for 60’; 125% for 10’; 150% for 1’ | |||||
BATTERIES |
||||||
Type | VRLA AGM / GEL; NiCd; Li-ion; | |||||
Residual ripple voltage | < 1% | |||||
Temperature compensation | (-0,5) Vx°C | |||||
Typical charge current | 0,2 x C10 | |||||
INFO FOR INSTALLATION |
||||||
Weight | 600 | 610 | 690 | 790 | ||
Dimensions (WxDxH) (mm) | 800 x 800 x 1900 | |||||
Remote signals | dry contacts | |||||
Remote controls | ESD and bypass | |||||
Communications | Double RS232 + dry contacts + 2 slots for communications interface | |||||
Operating temperature | 0 – 40 ° C | |||||
Relative humidity | <95% non-condensing | |||||
Colour | Dark grey RAL 7016 | |||||
Noise level at 1 m (ECO Mode) | 65 dBA | 68 dBA | ||||
IP rating | IP20 | |||||
Smart Active efficiency | έως 98% | |||||
Standards | Directives LV 2006/95/EC – 2004/108/EC; Safety IEC EN 62040-1;
EMC IEC EN 62040-2; Performance IEC EN 62040-3 |
|||||
Classification in accordance
with IEC 62040-3 |
(Voltage Frequency Independent) VFI – SS – 111 | |||||
Moving the UPS | transpallet |