Neo Pro+ RT UPS uses double conversion technology to provide clean, high level quality power to fully protect mission-critical devices such as communications networks, small computer centers, servers, telecoms applications and industrial applications.
Wide input voltage range (110 V -300 V)
Neo Pro+ RT provides stable power to connected devices under unstable power environments.
Output power factor 0.9
Neo Pro+ RT is a high-density UPS with output power factor 0.9 to provide higher performance and efficiency to critical applications.
DSP technology
A DSP controller provides an improved and cost-effective solution with high performance.
Αctive power factor correction in each phase
The power factor correction is active at all periods and increases the input performance.
ECO mode operation for energy saving
Offers efficiency up 97% to reduce energy usage & operation cost. UPS Neo Pro+ RT supplies the loads via static bypass, timely returning to online double conversion when the need arises.
50/60 Hz Frequency Converter Mode
Lock output frequency at 50Hz or 60Hz to supply power sensitive equipments.
SNMP + USB + RS-232 multiple communications
The communication of the UPS Neo Pro+ RT is done via the USB or RS-232 and also with SNMP interface.
Pure sine wave output
With pure sine wave output, Neo Pro+ RT series guarantees compatibility for all kinds of loads.
Rack/Tower
Neo Pro+ RT can be installed on Tower or in a 19′ Rack Cabinet for the 1-3 KVA models.
MODELS |
Neo Pro+ 1K RT |
Neo Pro+2K RT |
Neo Pro+3K RT |
Neo Pro+ 6K RT |
Neo Pro+ 10K RT |
|||
PHASE |
Phase 1 phase in / 1 phase out |
|||||||
CAPACITY |
1000 VA / 900 W |
2000 VA / 1800 W |
3000 VA / 2700 W |
6000 VA/ 5400 W |
10000 VA/ 9000 W |
|||
INPUT |
||||||||
Nominal voltage |
208/220/230/240 VAC |
208/220/230/240 VAC |
||||||
Input voltage range |
120-300 VAC (load 50%) 180-300 VAC (load 100%) |
110-300 VAC (load 50%) 176-300 VAC (load 100%) |
||||||
Frequency range |
40 ~ 70 Hz |
46-54 Hz or 56-64 Hz |
||||||
Power Factor |
≥ 0.99 |
|||||||
OUTPUT |
||||||||
Output voltage |
208/220/230/240 VAC |
208/220/230/240 VAC |
||||||
Voltage variation |
±1% |
|||||||
Frequency range (Synchronized Range) |
47 ~ 53 Hz or 57 ~ 63 Hz |
46 ~ 54 Hz or 56 ~ 64 Hz |
||||||
Frequency range (Batt.mode) |
50 Hz or 60 Hz ± 0.5% |
50 Hz or 60 Hz ± 0.1 Hz |
||||||
Crest Factor |
3 : 1 |
|||||||
Harmonic Distortion |
≤ 3% THD (linear load) |
≤ 3% THD (linear load) |
||||||
≤ 6% THD (non linear load) |
≤ 5% THD (non linear load) |
|||||||
Transfer Time |
AC Mode to Batt. Mode |
0 ms |
0 ms |
|||||
Inverter to Bypass |
4 ms (Typical) |
0 ms |
||||||
Waveform (Batt. Mode) |
Pure sine wave |
|||||||
EFFICIENCY |
||||||||
AC mode |
88% |
89% |
90% |
92% |
93% |
|||
Battery mode |
83% |
87% |
88% |
90% |
91% |
|||
BATTERIES |
||||||||
Type |
12 V / 9 Ah |
12 V / 9 Ah |
12 V / 9 Ah |
12 V / 9 Ah |
||||
Number |
2 |
4 |
6 |
16 |
20 |
16 |
20 |
|
Typical Recharge Time |
4 hours recover to 90% capacity |
9 hours recover to 90% capacity |
||||||
Charging Current (max.) |
1 Α |
1 Α / 2 Α |
||||||
Charging Voltage |
27.4 VDC ±1% |
54.7 VDC ±1% |
82.1 VDC ±1% |
218.4 VDC ±1% |
273 VDC ±1% |
218.4VDC ±1% |
273 VDC ±1% |
|
INDICATORS |
||||||||
LCD |
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
|||||||
ALARMS |
||||||||
Battery Mode |
Sounding every 4 seconds |
|||||||
Low Battery |
Sounding every second |
|||||||
Overload |
Sounding twice every second |
|||||||
Fault |
Continuously sounding |
|||||||
PHYSICAL |
||||||||
Dimension, D X W X H (mm) |
310 x 438 x 88 (2U) |
410 x 438 x 88 (2U) |
630 x 438 x 88 (2U) |
UPS Unit: 500x438x88{2U} Battery Pack: 668x438x88 [2U] |
UPS Unit: 580x438x133[3U] Battery Pack: 580x438x133 [3U] |
UPS Unit: 580x438x133[3U] Battery Pack: 580x438x133 [3U] |
||
Net Weight (kgs) |
12 |
19 |
29.3 |
UPS Unit: 15 Battery Pack: 61 |
UPS Unit: 18 Battery Pack: 51 |
UPS Unit: 18 Battery Pack: 61 |
||
ENVIRONMENT |
||||||||
Humidity & Temperature |
20-90 % RH @ 0- 40°C (non-condensing) |
0-95 % RH @ 0- 40°C (non-condensing) |
||||||
Noise Level |
<50dBA @ 1 meter |
<55dBA @ 1 meter |
<58dBA @ 1 meter |
|||||
COMMUNICATION |
||||||||
Smart RS-232 / USB |
Supports Windows 7/8/10, Linux and MAC |
|||||||
SNMP |
Power management from SNMP manager and web browser |