2109966555
Fax: +30 210 9969444
E-mail: info@acepower.gr
Home » Products » UPS » Industrial UPS » Master Industrial (30 – 80 KVA)
Master Industrial series UPS provide maximum protection and power quality for any type of load, especially industrial applications, such as manufacturing and petrochemical processes, electrical distribution and power plants. Master Industrial is an on-line double conversion UPS (class VFI SS 111 in accordance with IEC EN 62040-3) with input and output isolation transformers.
Industrial environment
Master Industrial is suited to the most demanding installation environments where there are vibrations, mechanical stresses, dust and in general where operating conditions are unfavourable to products created for the standard UPS market.
High ICC
The high short-circuit current (ICC = 3xIn) makes it suitable for loads that require high current peaks during switch-on or during normal operation.
DC voltage 220 V
The input and inverter transformers guarantee the isolation of the batteries, which are sized for a voltage of 220 VDC (from 108 to 114 elements), the standard industrial value.
Redundant ventilation
Redundant ventilation at 100% load is standard, ensuring operation with a normal load with half of the fans operating; in addition, each fan is monitored and an alarm signal is provided in the event of failure.
The Easy Source input features, the Battery Care System, and the flexibility and communications capabilities are the same as those of the conventional Master MPS range.
MODELS | ΜIM 30 | MIM 40 | ΜIM 60 | MIM 80 | ||
INPUT |
||||||
Nominal voltage | 380 – 400 – 415 VAC three-phase | |||||
Voltage tolerance | 400 V ± 20% | |||||
Frequency | 45 – 65 Hz | |||||
Power factor | > 0,93 | |||||
Current distortion | <6% | |||||
Soft start | 0 – 100% in 120’’ configurable | |||||
Permitted frequency tolerance | ± 2% (selectable from ± 1% to ± 5% from front panel) | |||||
Standard equipment provided | Back Feed protection; separable bypass line; battery isolation | |||||
BATTERIES |
||||||
Type | VRLA AGM / GEL; NiCd | |||||
Number of cells | 108/114 | |||||
Maximum charging voltage | 274 V | |||||
Temperature compensation | (-0,5) Vx°C | |||||
OUTPUT |
||||||
Nominal power (KVA) | 30 | 40 | 60 | 80 | ||
Active power (KW) | 24 | 32 | 48 | 64 | ||
Nominal voltage | 230 VAC single-phase | |||||
Static stability | ± 1% | |||||
Dynamic stability | ± 5% | |||||
Voltage distortion | < 1% with linear load / < 3% with non-linear load | |||||
Frequency | 50 or 60 Hz (selectable) | |||||
Crest factor | 3:1 lpeak/lrms | |||||
Overload | 110% for 60’; 125% for 10’; 150% for 1’ | |||||
Short-circuit current | 3 x I nom | |||||
INFO FOR INSTALLATION |
||||||
Weight (kg) | 640 | 650 | 910 | 940 | ||
Dimensions (WxDxH) (mm) | 800 x 800 x 1900 | 1200 x 800 x 1900 | ||||
Remote signals | dry contacts | |||||
Remote controls | ESD and bypass | |||||
Communications | Double RS232 + dry contacts + 2 slots for communications interface | |||||
Operating temperature | 0 – 40 ° C | |||||
Relative humidity | <95% non-condensing | |||||
Colour | Light grey RAL 7035 | |||||
Noise level at 1 m (ECO Mode) | 68 – 70 dBA | |||||
Ventilation | Redundant fans (front-top) | |||||
IP rating | IP20 | |||||
Efficiency | > 94% | |||||
Standards | Directives LV 2006/95/EC – 2004/108/EC; Safety IEC EN 62040-1; EMC IEC EN 62040-2; Performance IEC EN 62040-3 | |||||
Classification in accordance
with IEC 62040-3 |
(Voltage Frequency Independent) VFI – SS – 111 | |||||
Moving the UPS | transpallet |