facebook
Othonos 39, 17343
Agios Dimitrios Athens
Mon-Fri
09:00 - 17:00

Dentinel Dual Marine (6–10 kVA/kW)

Sentinel Dual Marine (6–10 kVA/kW)

UPS for Marine and Offshore Applications

Key Features

  • Power factor 1 kW = kVA
  • Parallel operation of up to 3 units
  • Designed for marine, offshore and demanding environments
  • DNV Type Approval
  • Flexible Tower or Rack installation
  • Selectable operating modes
  • High-quality output voltage
  • High battery reliability

The Sentinel Dual Marine (SMU) is designed to power critical applications that require high reliability and continuity of power in marine, offshore and other demanding environments.

The range is available in 6 and 10 kVA/kW models, with a power factor of 1 and ON LINE double-conversion technology (VFI). The load is continuously supplied by the inverter with a sinusoidal output voltage, filtered and stabilised in terms of voltage, waveform and frequency.

The ability to install the system in either Tower or Rack configuration, combined with dedicated anti-vibration solutions, conformal coating of the electronic boards and multiple communication options, makes the Sentinel Dual Marine suitable for applications where electrical and electronic equipment is exposed to increased environmental and mechanical stress.

Up to three units can operate in parallel, either to increase the available power or in an N+1 redundant configuration, increasing the availability of critical loads.

The range has DNV Type Approval in accordance with DNV-CG-0339 for the specified installation configurations.

ACE Power Electronics – Official Riello UPS Distributor in Greece

Product Description

Technical Specifications

Product Brochure

Features

High Reliability in Marine Environments

The Sentinel Dual Marine has been designed and built to meet the specific requirements of marine, offshore and other demanding installations, where an interruption to the power supply may affect critical navigation, communication, automation and safety equipment.

For Tower installations, dedicated anti-vibration frames are available to reduce the transmission of continuous vibrations caused by engines, waves and vessel movement. In Rack applications, installation is carried out in suitable cabinets equipped with a vibration damping system.

The internal electronic printed circuit boards (PCBs) also undergo a conformal coating treatment, providing enhanced protection for electronic components in demanding operating conditions.

With the specified anti-vibration configurations, the system meets DNV-CG-0339 Class A vibration requirements.

Simplified and Flexible Installation

The Sentinel Dual Marine can be installed either as a floor-standing Tower unit with the appropriate anti-vibration frame or in a Rack cabinet, providing installation flexibility according to the available space and system architecture.

The rotatable display enables easy operation in both configurations. A low noise level of less than 48 dBA in ECO Mode is achieved through a high-frequency switching inverter and a digitally controlled fan system that adjusts according to the load.

The UPS also supports an external maintenance bypass for maintenance operations without interruption to the power supply, while operation is guaranteed at ambient temperatures of up to 45 °C. The integrated IEC output sockets are equipped with thermal protection.

Operating Mode Selection

Operating modes can be programmed via software or selected from the front display of the UPS.

ON LINE: VFI double-conversion operation, with efficiency up to 95%.

ECO Mode: increases energy efficiency up to 98%, using VFD operation where permitted by the application requirements.

SMART ACTIVE: the UPS evaluates the quality of the mains supply and automatically selects between VFD and VFI operation.

STANDBY OFF: the UPS powers the load when the mains supply fails, for emergency applications.

Frequency Converter: operation as a 50 or 60 Hz frequency converter.

High Battery Reliability and Management

The Sentinel Dual Marine incorporates functions designed for effective battery management and utilisation.

The SMU 6000 LA PDIST DVA version is equipped with internal Long Life VRLA AGM batteries, while both automatic and manual battery tests are supported.

The Low Ripple Current Discharge (LCRD) system reduces the ripple current component, which can negatively affect battery performance.

In the version with internal batteries, battery replacement can be carried out without switching off the protected equipment and without interrupting the power supply to the load (Hot Swap).

Battery Usage Optimisation

The wide input voltage range and high hold-up time reduce unnecessary battery intervention during short power disturbances.

For interruptions lasting less than 20 ms, as well as when the input voltage remains within the specified range, the system can maintain power without using the batteries. For very short interruptions, energy is supplied by appropriately sized capacitors.

This function helps reduce unnecessary discharge cycles and supports more effective use of the battery system.

Runtime Expandability

For applications requiring longer backup times, additional Battery Cabinets can be connected.

The range also includes ER versions without internal batteries and with a 6 A battery charger, designed for use with external battery systems and extended runtimes.

A Battery Cabinet with 15 × 9 Ah batteries is available for the 6 kVA model, while a Battery Cabinet with 20 × 9 Ah batteries is available for the 10 kVA model. Both solutions can be installed in Tower or 3U Rack configuration.

Emergency Function

The dedicated emergency function supports systems that require continuous and reliable power in the event of a mains failure, such as emergency lighting, fire detection and extinguishing systems, and alarm systems.

In the event of a mains failure, the inverter powers the loads with a progressive start-up (Soft Start), reducing the risk of overload during start-up.

EnergyShare

Programmable EnergyShare output sockets allow available runtime to be optimised through load priority management.

In the event of a power failure, lower-priority loads can be automatically disconnected so that the available battery energy is reserved for critical loads. Alternatively, specific emergency loads that remain inactive under normal mains conditions can be activated when required.

Advanced Communications

The Sentinel Dual Marine is equipped with USB and RS232 ports, as well as a slot for optional communication cards.

It supports PowerShield³ software for monitoring and safe shutdown of connected systems, together with additional Riello UPS communication and network monitoring solutions.

Operating status, measurements and alarms are also available through the integrated UPS display.

Unity Power Factor

With an output power factor of 1, the rated apparent power in kVA corresponds to the actual active power in kW.

The 6 kVA model therefore provides up to 6 kW of active power, while the 10 kVA model provides up to 10 kW, allowing full utilisation of the UPS rated power.

Standards and Certifications

The Sentinel Dual Marine complies with IEC EN 62040-1 for UPS safety, IEC EN 62040-2 for electromagnetic compatibility and IEC EN 62040-3 for performance requirements and test methods.

Its classification according to IEC 62040-3 is VFI-SS-111.

It has DNV Type Approval in accordance with DNV-CG-0339, Certificate No. TAE 00004YU. For vibration Class A, the specified anti-vibration configurations apply.

2-year warranty included!

MODELS SMU 6000 LA PDIST DVA SMU 6000 ER DVA SMU 10000 DI ER DVA
INPUT
Dual Input no yes
Rated voltage [V] 220 / 230 / 240
Voltage tolerance [V] 230 ±20%
Minimum voltage [V] 184
Rated frequency [Hz] 50 / 60 ±5
Power factor >0.98
Current distortion ≤2%
BYPASS
Voltage tolerance [V] 180 / 264 (selectable in ECO Mode or SMART ACTIVE Mode)
Frequency tolerance Selected frequency ±5% (selectable by user)
Overload Times <110% continuous, 130% for 1 h, 150% for 10 min, over 150% for 3 s
OUTPUT
Nominal power [VA] 6000 6000 10000
Active power [W] 6000 6000 10000
Rated voltage [V] 220 / 230 / 240 selectable
Voltage distortion <1% with linear load / <3% with non-linear load
Frequency [Hz] 50 / 60 selectable
Static variation 1.5%
Dynamic variation ≤5% in 20 ms
Waveform Sinusoidal
Crest factor [Ipeak/Irms] 3:1
BATTERIES
Type VRLA AGM maintenance-free lead based, Long life, UL94-V0
Recharge time 4-6 h
OVERALL SPECIFICATIONS
Net weight [kg] 46 20 21
Gross weight [kg] 54 28 25
Dimensions (WxDxH) [mm] 131x640x448
Packaging dimensions

(WxDxH) [mm]

800x600x(240+120) 2x (800x600x240) + 120

ER version 800x600x(240+120)

Efficiency up to 95% ON LINE Mode, 98% ECO Mode
Protections Overcurrent – short circuit – overvoltage – undervoltage – temperature – excessive low battery
Parallel Operation Optional Parallel Card
Communications USB / RS232 / slot for communications interface / R.E.P.O. + Input contact
Input Connection Terminal board
Output sockets Terminal board + 2x IEC 320 C13 (10 A) + 3x IEC 320 C19 (16 A)
Standards European directives: LV 2014/35/EU low voltage Directive EMC 2014/30/EU electromagnetic compatibility Directive

Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant

Classification in accordance with IEC 62040-3 (Voltage Frequency Independent) VFI – SS – 111

DNV Type Approval according to DNV-CG-0339 July 2025 (Certificate No. TAE 00004YU)

Ambient temp. for the UPS 0 °C – +45 °C
Recommended temperature

for battery life

+20 °C – +25 °C
Range of relative humidity 5-95% non-condensing
Colour RAL 9006
Noise level at 1 m

(ECO Mode) [dBA]

<48
Standard equip. provided USB cable; handles kit

View the PDF here

CALL US
CONTACT US
ACE Power Electronics
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.