Home » Products » Transfer Systems » Master Switch STS
Installing a Master Switch static transfer switch provides additional resilience and protection from the disruption that can be caused by the failure of a single power source. The result is the absolute protection of industrial utilities and critical information technology against power supply and load faults.
Operating principle
Master Switch guarantees a source of redundant power, allowing the load to be switched between to alternative and independent power sources.
Switching can be automatic (when a supply source falls outside of acceptable tolerances) or manually done by an operator from the front panel or remotely.
Protection against power supply faults
If one of the two power sources falls outside tolerance levels, Master Switch will transfer the consumers to the second power source (switching is instantaneous if the two sources are in phase).
Protection against environmental disturbances
Overloads and load faults
In the event of an overload, the user can decide the level of intervention of the internal protection devices in order to block the power supply. In the extreme case of a downstream short circuit, Master Switch disconnects the load in order to avoid jeopardising the operation of the other loads (i.e. in the event of poor selectivity of the protection devices).
Total microprocessor control
Microprocessor control logic ensures:
Redundant design
Power is supplied to the internal logic by two physically separate supply circuits that are fully independent and that can be replaced in “hot replacement” mode without causing power supply interruptions to the load. In the event that the power supplied by both sources fails, full system operation is guaranteed by the “Power Supply back up” function, which provides auxiliary power supply to the circuits from an external, independent power source.
Master Switch is equipped with a dual redundant ventilation system known as: “fan redundance plus”. Thanks to this feature, and in the unlikely event that two fans fail at the same time, those remaining would still be able to dissipate the heat generated at nominal load and with an ambient temperature of up to 40° C. Also the fans can be replaced in “hot replacement” mode, ensuring continuity during the replacement operation.
Superior protection
In the event of an output short circuit, Master Switch blocks the transfer between the two power sources, eliminating the risk of propagating the short circuit and its effects to the other loads. A back feed control circuit ensures the automatic intervention of the protection devices when a return of power to one of the two Master Switch inputs is detected.
Accessibility
The layout of the moving components and parts is designed to ensure easy frontal access:
Advanced communications
Master Switch provides information, measurements, statuses, and alarms via the LCD display. The STS is compatible with PowerShield3 supervision and shutdown software for Windows operating systems 8, 7, Hyper-V, 2012, 2008, and previous versions, Mac OS X, Linux, VMWare ESXi, Citrix XenServer and other Unix operating systems.
MODELS | MTS 100 | MTS 150 | MTS 200 | MTS 250 | MTS 300 | MTS 400 | MTS 600 | MTS 800 |
NOMINAL CURRENT | 100 A | 150 A | 200 A | 250 A | 300 A | 400 A | 600 A | 800 A |
INPUT |
||||||||
Nominal voltage – sources S1/S2 | 380 – 400 – 415 VAC three-phase + N | |||||||
Input voltage tolerance | 180-264 VAC (selectable) | |||||||
Switched input phases | 3+N (4-pole) – 3 (3-pole) | |||||||
Nominal frequency | 50/60 Hz | |||||||
Input frequency tolerance
range |
+/-10% (selectable) | |||||||
Network compatibility | IT, TT, TNS, TNC | |||||||
OPERATION SPECIFICATIONS |
||||||||
Transfer type | “Break Before Make” | |||||||
Available transfer methods | Automatic / Manual / Remote | |||||||
Transfer time following source
failure |
< 4 msec (S1/S2 synchronised)
10 msec (S1/S2 non synchronised) |
|||||||
ENVIRONMENTAL SPECIFICATIONS |
||||||||
Efficiency at full load | > 99% | |||||||
Noise at 1 m from front (from 0 to full load) | 55 dBA | 55 dBA | 55 dBA | 55 dBA | 55 dBA | 55 dBA | 57 dBA | 62 dBA |
Operating temperature | 0 °C – 40 °C | |||||||
Relative humidity | 95% non-condensing | 5-95% non-condensing | ||||||
Max. installation height | 1000 m at nominal power (-1% power for every 100 m above 1000 m) – Max 4000 m | |||||||
Reference standard | EN 62310-1 (safety) EN 62310-2 (electro-magnetic compatibility) | |||||||
INFO FOR INSTALLATION |
||||||||
Weight (kg) | 155 | 160 | 205 | 210 | 235 | 240 | 375 | 560 |
Dimensions WxDxH (mm) | 685 x 530 x 1500 | 685 x 580 x 1770 | 950 x 730 x
1900 |
1250 x 850 x 1905 | ||||
Color | RAL 7016 | RAL 7024 | ||||||
IP rating | IP 20 | |||||||
Moving the STS | Transpallet |