Rectifiers-Chargers

Rectifiers-Chargers

ACE Power Electronics provides in the Greek market Rectifiers – Chargers of branded Italian manufacturers. The models cover every direct current output requirement with single-phase or three-phase input and 12V or 24V or 48V or 110V or 220V DC output. The available models start from a minimum Ampere output current and can meet any requirement requested.

 

                                             Indicative design of dual Rectifier-Charger of batteries

 

 

Features

Technical Specifications

MAIN FEATURES

  • IGBT or Thyristor, depending on power
  • Isolation transformer on AC input line
  • System control with industrial plc
  • Touchscreen panel
  • Charging curve for AGM – PB – NiCd battery
  • 3 charging levels including manual charging
  • High MTBF and low MTTR
  • Easy maintenance with access from the front
  • Low ripple in output and on batteries (ripple)
  • Temperature compensation and corrector coefficient
  • Automatic battery test with programmable frequency

APPLICATIONS

  • Oil & Gas (petrochemical plants, offshore, pipeline)
  • Electricity generation (power stations, hydroelectric, transmission, distribution, utilities)
  • Transport (Airports, naval, rail)
  • Mining industry, steel mills, railways etc.

 

Table of indicative technical characteristics 

 

    IGBT THYRISTOR
Output voltage Vcc

  24 48 110 24 48 110 220
Input Voltage 1 Ph 230 Vac ± 10% NOT AVAILABLE
  3 Ph 400 Vac ± 10%
Entry Frequency   50 ÷ 60 Hz ± 5%
Input Voltage – Icc

  ≤ 10KA RMS (with standard IEC-nominal main input)
Current Input Distortion THD ≤ 27 (with nominal load)
Input power factor   0.80 (With nominal voltage 100% load)
I/O isolation   4kV with transformer

OUTPUT DATA

Output current

Input type 1 Ph

10÷60 Α

 
 

Input type 3 Ph

10÷100 Α

100÷500 Α

10÷250 Α

Battery charging

voltage

Floating

(settable from HMI)

2,27 V/cell for VRLA battery type

2,2 ÷ 2,3 V/cell for VLA battery type

1,4 ÷ 1,5 V/cell for Ni-Cd battery type

Boost (settable from HMI)

2,4 ÷ 2,45V/cell for VLA battery type

1,5 ÷ 1,65V/cell for Ni-Cd battery type

Manual

(settable from HMI)

2,35 V/cell for VRLA battery type

2,7 V/cell for VLA battery type

1,7 V/cell for Ni-Cd battery type

Current battery charging

(settable from HMI)

1 ÷ In Α

Output voltage stability  (ref. INPUT MAIN VAR.)

1%

Output voltage stability  (ref. LOAD VAR.)

1%

Output ripple

RMS

1%

Overload

(without battery)

2 In x 5 mS

<120% per 20 min

>150% per 5 sec

ENVIRONMENTAL DATA

Noise level Ref. EN50091 < 60 dBA (typical value with forced ventilation in operation)  
ΕMI   EN 61000-6-2 – EN 61000-6-4  
Operating temperature °C -10………. +40  
Storage temperature °C -20………..+70  
Relative humidity without condensation < 95%  
Ventilation

(on AC/DC conversion module)

  Electronic temperature speed control FORCED
Altitude Mt.sl.m. < 1000 (derating according EN62040-3)  

MECHANICAL DATA

Degree of protection – external Ref. IEC 60259 IP 31 standard – others on request  
Degree of protection – internal Ref. IEC 60259 IP 20 with open front door and additional protections inserted  
IN/OUT cable connections   From the front with cable input from below  
Transportation   Base for handling with forklift  
Installation   From the floor  
Accessibility   Front  

PROTECTIONS

Input   Automatic Circuit Breacker  
Output   Manual Isolator  
Battery   Fuses  