The range Neo 3/1 uses double conversion technology to provide clean, high level quality power to fully protect mission-critical devices such as communications networks, small computer centers, servers, telecoms applications and industrial applications.
Wide input voltage range (110V-300V)
Neo 3/1 can provide stable power to connected devices under unstable power environments.
Programmable power management outlets
With programmable power management outlets, users can easily and independently control load segments. During power failure, this feature enables users to extend battery time to mission-critical devices by shutting down the non-critical devices.
ECO mode operation for energy saving
Offers efficiency up to 97% to reduce energy usage & operation cost. UPS supplies the loads via static bypass, timely returning to online double conversion when the need arises.
50/60 Hz Frequency Converter Mode
Lock output frequency at 50Hz or 60Hz independently of the input frequency.
Emergency Power Off (EPO) Function
This feature can secure the personnel and equipment in case of emergency.
Maintenance bypass
Internal maintenance bypass assures power continuity to critical devices during UPS maintenance.
Parallel
Neo 3/1 can be used in parallel operation with up to 3 units. This function increases power capacity, safety and availability.
Smart battery charger design to optimize battery performance
Neo 3/1 are equipped with 3-stage charger for optimized battery performance. This feature extends the useful service life of batteries and optimizes battery recharge time.
SNMP + USB + RS-232multiple communications
This feature allows either USB or RS-232 communication port to work with SNMP interface simultaneously.
MODELS | Neo 3/1 10Κ | Neo 3/1 20K | ||||
PHASE | 3 phase in / 1 phase out | |||||
CAPACITY | 10000VA / 8000W | 20000VA / 16000W | ||||
INPUT |
||||||
Voltage Range
|
Low Line Range | 176 VAC (phase voltage) @ 100% load | ||||
110 VAC (phase voltage) @ 50% load | ||||||
Low Line Comeback | 186 VAC (phase voltage) @ 100% load 120 VAC (phase voltage) @ 50% load | |||||
High Line Transfer | 300 VAC (phase voltage) | |||||
High Line Comeback | 290 VAC (phase voltage) | |||||
Frequency Range | 46~54Hz or 56~64Hz | |||||
Power Factor | < 0.99 @ 100% load | |||||
OUTPUT |
||||||
AC Voltage Regulation (Batt. Mode) | ± 1% | |||||
Frequency Range (Synchronized Range) | 46~54 Hz or 56~64 Hz | |||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |||||
Current Crest Ratio | 3:01 | |||||
Harmonic Distortion | < 2 % THD (Linear Load) | |||||
< 6 % THD (Non-linear Load) | ||||||
Transfer Time | AC Mode to Batt. Mode | Zero | ||||
Μεταγωγής | Inverter to Bypass | Zero | ||||
Waveform (Batt. Mode) | Pure Sinewave | |||||
EFFICIENCY |
||||||
AC Mode | 90% | |||||
Battery Mode | 88% | |||||
BATTERY |
||||||
Battery Type | 12 V / 9 Ah | 12 V / 9 Ah | ||||
Numbers | 20 | 20 x 2 | ||||
Typical Recharge Time | 9 hours recover to 90% capacity | |||||
Charging Current (max.) | 1Α | |||||
Charging Voltage | 273 VDC ± 1% | |||||
INDICATORS |
||||||
LCD Panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |||||
ALARM |
||||||
Battery Mode | Sounding every 4 seconds | |||||
Low Battery | Sounding every second | |||||
Overload | Sounding twice every second | |||||
Fault | Continuously sounding | |||||
PHYSICAL |
||||||
Dimension, H x W x D (mm) | 576 x 250 x 592 | 826 x 250 x 862 | ||||
Net Weight (kgs) | 86 | 139 | ||||
ENVIRONMENT |
||||||
Humidity | 20-90 % RH @ 0- 40°C (non-condensing) | |||||
Noise Level | < 58dB @ 1 Meter | |||||
COMMUNICATION |
||||||
Smart RS-232/USB | Supports Windows 98/2000/2003/XP/Vista/2008, Windows 7, Linux and MAC | |||||
Optional SNMP | Power management from SNMP manager and web browser |